Definition
Percentage of baseline heat-transfer capacity restored after each cleaning event, tracked over successive cleaning cycles, with a companion Permanent Fouling Rate (PFR) that quantifies the per-cycle decline: detecting whether cleaning is returning the exchanger to reference performance or whether a permanent fouling layer is building up beneath what cleaning can remove.
The Measurement Gap
Heat exchanger cleaning programs run on schedule. The model says clean every six months. The maintenance system records that the cleaning happened. The performance dashboard records a step improvement in heat transfer. Everything works as designed. What no legacy metric captures is whether each successive cleaning is restoring the same fraction of baseline performance. Pre-cleaning heat-transfer coefficient measures dirty performance. Post-cleaning heat-transfer coefficient measures clean performance but only against the current dirty baseline, not against the original design. Maintenance compliance counts cleaning events without asking whether each event achieved the same result. Energy intensity drifts upward over years as the permanent fouling layer accumulates, but the drift is attributed to feedstock changes, weather, or other slow variables. The signature pattern (a step recovery after each cleaning that is slightly lower than the previous step) is invisible without explicit cycle-by-cycle comparison.
Decision Supported:
Is the cleaning schedule maintaining heat-transfer capacity, or is each clean-to-dirty cycle starting from a lower baseline, and if so, how many cycles until mechanical cleaning, bundle replacement, or redesign?
Formula
Plain language: After each cleaning, measure the overall heat-transfer coefficient and divide by the baseline U-value from the clean, new, or post-mechanical-cleaning reference. Multiply by one hundred. Track the trend across cleaning cycles. The companion PFR quantifies how much baseline performance the exchanger has lost per cycle.
Notation:
CEDI = ( U_post_clean_n / U_baseline ) × 100
PFR = ( U_baseline − U_post_clean_n ) / n_cleaning_cycles
Variables:
| Variable | Definition | Unit |
|---|---|---|
| U_post_clean_n | Overall heat-transfer coefficient measured immediately after cleaning event n | BTU/hr·ft²·°F or W/m²·K |
| U_baseline | Heat-transfer coefficient at the reference condition (clean, new, or post-mechanical-cleaning) | BTU/hr·ft²·°F or W/m²·K |
| n | Index of cleaning event in the exchanger's service history | n/a |
| PFR | Permanent Fouling Rate: average loss of baseline capacity per cleaning cycle | (BTU/hr·ft²·°F) / cycle |
Proposed formula, pending validation pilots.