Definition
DET measures the extra energy consumed because an asset operates in a degraded condition compared to a healthy equivalent at the same load and operating context.
The Measurement Gap
Asset degradation that does not cause failure is invisible to legacy maintenance metrics. OEE was designed to measure output against theoretical capacity: it cannot answer whether the asset is consuming excess energy to produce that output. A compressor at rated throughput with 25% excess current draw scores the same OEE as a healthy compressor. MTBF counts failures, not degraded-but-functional states. PM Compliance confirms scheduled work happened but says nothing about whether the asset is running efficiently between PMs. The U.S. DOE has documented for decades that motor-driven systems account for roughly 70% of industrial electricity consumption and that maintenance-addressable inefficiencies (bearing wear, fouling, leaks, misalignment) drive significant energy waste, but no maintenance KPI measures it at the asset level.
Decision Supported:
Whether to schedule a condition-based intervention on an asset whose throughput is acceptable but whose energy draw indicates degradation.
Formula
Plain language: For each time interval, measure actual power consumption and subtract the power a healthy asset would draw at the same load and operating context. Sum the gap across the period; multiply by the energy cost rate for the monetized form.
Notation:
DET = Sigma_t [ P_actual(t) - P_baseline(healthy, load_t, context_t) ] x Delta_t
DET_cost = DET x EnergyRate
Variables:
| Variable | Definition | Unit |
|---|---|---|
| P_actual(t) | Measured power consumption of the asset at interval t | kW |
| P_baseline(healthy, load_t, context_t) | Expected power consumption of the same asset in healthy condition at the same load and context | kW |
| Delta_t | Length of each time interval | hours |
| EnergyRate | Blended energy cost rate | $/kWh |
| DET | Excess energy consumed due to degradation | kWh |
| DET_cost | Monetized degradation energy tax | $ |
A companion metric, Micro-Inefficiency Closure Yield (MICY), flips perspective: MICY = Sigma VerifiedEnergySaved / Sigma EstimatedEnergyBleed, capturing the fraction of identified energy-loss defects actually closed and verified.
Proposed formula, pending validation pilots.